Monarch Escalator Fault

Monarch Escalator Fault Code Table

Error Code Troubleshooting Note (the number before the fault description is the fault subcode)
Err1 Overspeed 1.2 times During normal operation, the operating speed exceeds 1.2 times the nominal speed.Appears during debugging, please confirm whether the FO group parameter settings are abnormal
Err2 1.4 times faster During normal operation, the operating speed exceeds 1.4 times the nominal speed.Appears during debugging, please confirm whether the FO group parameter settings are abnormal
Err3 non-manipulated reversal Non-manipulated reversal of elevator speed
This fault occurs during debugging, please check whether the ladder speed detection signal is reversed (X15, X16)
Err4 Brake stop over distance fault The stopping distance exceeds the standard requirement
Appears during debugging, please confirm whether the FO group parameter settings are abnormal
Err5 left armrest underspeed Left handrail underspeed
Improper setting of group F0 parameters
Abnormal sensor signal
Err6 Right handrail underspeed Right handrail underspeed
Improper setting of FO group parameters
Abnormal sensor signal
Err7 upper rung missing The upper rung is missing, check whether the value of FO-06 is less than the actual value
Err8 lower rung missing The lower rung is missing, check whether the value of FO-06 is less than the actual value
Err9 Working brake opening failure Abnormal working brake signal
Err10 Additional brake action failure 1: Mechanical switch feedback is invalid after braking
2: The additional brake switch is valid when starting
3: The additional brake is not opened when starting
4: When the additional brake switch is valid, the uplink starts running for more than 10 seconds
5: The additional brake switch is valid during running
6: The additional brake contactor is disconnected during operation
Err11 Faulty floor cover switch Under normal conditions, the cover switch signal is valid
Err12 Abnormal external signal 1: There is AB pulse in the parking state
2: There is no AB pulse within 4 seconds after starting
3: The AB signal between the upper step signals is less than the set value of FO-O7
4: The AB signal between the lower step signals is less than the set value of FO-07
5: The pulse of the left armrest is too fast
6: The pulse of the right armrest is too fast
7: The two maintenance signals are inconsistent
8: Uplink and downlink signals are valid at the same time
Err13 PES board hardware failure 1~4: Relay feedback error
5: eeprom initialization failed
6: Power-on RAM check error
Err14 eeprom data error none
Err15 Main shop data verification abnormality or MCU communication abnormality 1: The software versions of the main and auxiliary MCUs are inconsistent
2: The status of the main and auxiliary chips is inconsistent
5: The output is inconsistent
6: The speed of phase A is inconsistent
7: Phase B elevator speed inconsistent
8: The orthogonality of the AB pulse is not good, and there is a jump
9: The braking distance detected by the main and auxiliary MCUs is inconsistent
10: The signal of the left armrest is unstable
11: The signal of the right armrest is unstable
12.13: The upper step signal is unstable
14.15: Down step signal is unstable
101~103: Communication error between main and auxiliary chips
104: Main and auxiliary communication failure after power-on
201~220: X1~X20 terminal signal unstable
Err16 Parameter exception 101: Calculation error of pulse number 1.2 times of maximum braking distance
102: AB pulse number calculation error between steps
103: The calculation of the number of pulses per second is wrong

 

Escalator failure phenomenon

Fault Code Fault Symptoms
Err1 Speed exceeds nominal speed by 1.2 times ◆LED flashing
◆The fault number output interface outputs the fault number
◆After connected to the manipulator, the manipulator will display the fault number
◆Response remains the same after re-powering
Err2 Speed ​​exceeds nominal speed by 1.4 times
Err3 Non-manipulated reverse operation
Err7/Err8 Missing rungs or treads
Err9 After starting, the service brake does not open
Err4 The stopping distance exceeds 1.2 times the maximum allowable value
Err10 Additional brake action failure ◆The reaction is consistent with the above fault, but it can be restored to normal state after power on again
Err12/13/14/15 Abnormal signal or self-failure
Err5/Err6 The speed of the handrail deviates from the actual speed of the step tread or tape by more than -15%
Err11 Check for opening of the access panel in the bridge area or opening or removal of the floor plate ◆The response is the same as the above-mentioned fault, but it can be reset automatically after the fault disappears

 